Architectural
Specifications - WCF-50
|
ENGLISH |
|
Fiberglass shall be as outlined in the North American
Insulation Manufacturing Association (NAIMA 202-96) specification,
or equal, with an R-value of ______ when not compressed. The
fiberglass shall be faced with ______, as specified below, on one
side. The composite of fiberglass and facing shall have
surface burning characteristics not to exceed 25 flame spread and 50
smoke developed when tested in accordance with Underwriters
Laboratories 723 test method or ASTM E 84 test method.
Facing shall be composed of 0.0003” white coated aluminum foil with an
elastomeric vapor barrier coating, a proprietary inner core, a reinforcing
layer, and 0.0005” metallized polyester film. The product shall be reinforced
with a 5x5 tri-directional scrim which has a blend of fiberglass and polyester
yarns. The resulting facing shall have a water vapor transmission rate of 0.02
US perm (ASTM E96, Procedure A), a beach puncture of 90 scale units and a mullen
burst of 100 P.S.I. Tensile strength shall be 60# in the machine direction and
55# in the cross-machine direction.
|
|
METRIC |
|
Fiberglass shall be as outlined in the North American
Insulation Manufacturing Association (formerly T.I.M.A )
specification, or P.E.B. 202 or equal, with an R-value of ______
when not compressed. The fiberglass shall be faced on one
side. The composite of fiberglass and facing shall have
surface burning characteristics not to exceed 25 flame spread and 50
smoke developed when tested in accordance with Underwriters
Laboratories 723 test method or ASTM E 84 test method.
Facing shall be composed of 7.6 micron white coated aluminum foil with an
elastomeric vapor barrier coating, a proprietary inner core, a reinforcing
layer, and 12.7 micron metallized polyester film. The product shall be
reinforced with a 20/100 mm x 20/100 mm tri-directional scrim which has a blend
of fiberglass and polyester yarns. The resulting facing shall have a water
vapor transmission rate of 1.15 ng/N.s (ASTM E96, Procedure
A), a beach puncture of 2.7 Joules and a mullen burst of 7.0 kg/cm². Tensile
strength shall be 10.5 kN/m in the machine direction and 9.6 kN/m in the
cross-machine direction
|
|