Technical Bulletin #17:
(PDF VERSION)
Long Tab with Banding - High-R Insulation System Test Results
The Long Tab with Banding installation method is also referred to as a
“Filled Cavity System” (FC) in ASHRAE
literature.

A graphic of the installation is to the right.
Thermal testing of the Long Tab with Banding / Filled Cavity
System was conducted in October 2010 and January 2011 at the Butler
Manufacturing Research Center located in Grandview, MO, an independent certified
laboratory.
Testing was conducted in accordance with ASTM
C1363, “Standard Test Method for Thermal Performance of Building Materials and Envelope Assemblies by Means of a Hot Box Apparatus”
The results for the two assemblies tested were as follows:
Faced R19 fiberglass and R11 unfaced fiberglass
U-Value of 0.037
Faced R25 fiberglass and R19 unfaced fiberglass
U-Value of 0.029
Test reports can be downloaded at the following links:
Faced R19 F/G & R11 unfaced F/G - http://www.lamtec.com/cdocs/ButlerTestReport2010-49.pdf
Faced R25 F/G & R19 unfaced F/G -
http://www.lamtec.com/cdocs/ButlerTestReport2011-06.pdf
The benefits of Long Tab with Banding / Filled Cavity System are:
-
High- R / Low U-Values which meet most new energy standards. -
Non proprietary installation system -
Attractive installed appearance
-
Easy installation of electrical, HVAC and sprinkler systems -
Economical
A summary of the two tests follows:
|
Property |
Long Tab Banded/Filled Cavity System R-19/R11 |
Long Tab Banded/Filled Cavity |
|
Thermal Transmittance, U: |
0.209 W/m2 K |
0.166 W/m2 K |
|
(0.037 Btu/ hr ft2 F) |
(0.029 Btu/ hr ft2 F) |
|
|
Overall Thermal Resistance, Ru: |
4.8 m2 K/W |
6.0 m2 K/W |
|
(27.2 hr ft2 F/Btu) |
(34.1 hr ft2 F/Btu) |
|
|
Upper Fiberglass |
Nominal R-11 unfaced NAIMA 202-96 fiberglass blanket insulation |
Nominal R-19 unfaced NAIMA 202-96 fiberglass blanket insulation |
|
Measured thermal resistance: 11.83 hr ft2 ºF/Btu |
Measured thermal resistance: 22.68 hr ft2 ºF/Btu |
|
|
Lower Fiberglass |
Nominal R-19 faced NAIMA 202-96 fiberglass blanket insulation |
Nominal R-25 faced NAIMA 202-96 fiberglass blanket insulation |
|
Measured thermal resistance: 20.69 hr ft2 ºF/Btu |
Measured thermal resistance: 24.04 hr ft2 ºF/Btu |
|
|
WMP-VR-R Plus facing |
WMP-VR-R Plus facing |