Technical Bulletin #16
CASE STUDY: Lamtec White Facings Reduce Lighting Investment Cost and Annual Electricity Costs
Objective: Compare the lighting fixture requirements and energy costs using Lamtec
white metal building facings versus a conventional galvanized metal roof deck.
Project: Two (2) industrial facilities totaling 420,000 ft2, completed in 2010
Building 1- 260,000ft2 faced with WMP-50 in the roof
Building 2- 160,000ft2 faced with WMP-UV HD in the roof
Interior precast walls painted with eggshell off white finish
Specifications: Approximately 30 foot candles maintained illumination
T5HO high bay 6 lamp 324 watt wide distribution fluorescent
light fixtures with up-lighting
Ceiling height varies between 25 and 32 feet
Lighting installed at 22 ft. above finished floor
Light WMP-50 and WMP-UV HD light reflectance is 85%*
Reflectance: The plain galvanized metal roof deck light reflectance is 62%**
Summary:
|
Fixture Count |
Fixture Count |
Fixture |
kW |
Annual |
||
|
Plain Galvanized |
Lamtec White Facing |
Reduction |
Reduction |
Savings |
||
|
Building 1: |
260,000 ft2 |
544 |
434 |
110 |
42.27 |
$28,994 |
|
Building 2: |
160,000 ft2 |
322 |
264 |
58 |
22.27 |
$15,228 |
Calculations based on:
Hours of operation/year = (260 days/year)*(24 hours/day) = 6240 hours/year
Electricity Cost = $.11/kW hour
*The light reflectance of Lamtec facings is provided on the specification sheets available at www.lamtec.com
**Light reflectance determined in testing by Atlas Services Group on May 3rd, 2011.
Conclusions:
· Lamtec facings reduced the number of lighting fixtures required by 20% in Building # 1 and 18% in Building # 2; reducing the total investment cost in lighting fixtures.
· Lamtec facings reduced the annual lighting cost by $28,994/year in Building #1 and $15,288/year in Building # 2.
· Lamtec facings offer exceptional benefits for their outstanding light reflectivity when compared to a plain galvanized metal roof deck.
· As with any project, Lamtec recommends consulting your design engineer for your specific design criteria and lighting calculations.