Architectural
Specifications - GYMGUARD
|
ENGLISH |
|
Fiberglass shall be as outlined in the North American
Insulation Manufacturing Association (NAIMA 202-96) specification,
or equal, with an R-value of ______ when not compressed. The
fiberglass shall be faced with ______, as specified below, on one
side. The composite of fiberglass and facing shall have
surface burning characteristics not to exceed 25 flame spread and 50
smoke developed when tested in accordance with Underwriters
Laboratories 723 test method or ASTM E 84 test method.
Facing shall be composed of 0.0015" white metallized
polypropylene film laminated to a fiberglass/polyester blend fabric with a fire resistant
adhesive. The resulting facing shall have a water vapor transmission rate of 0.02 US perm
(ASTM E96, Procedure A), a beach puncture of 650 scale units and a mullen burst of 250
psi. Tensile strength shall be 195# in the machine direction and 150# in the cross-machine
direction. |
|
METRIC |
|
Fiberglass shall be as outlined in the North American
Insulation Manufacturing Association (formerly T.I.M.A )
specification, or P.E.B. 202 or equal, with an R-value of ______
when not compressed. The fiberglass shall be faced on one
side. The composite of fiberglass and facing shall have
surface burning characteristics not to exceed 25 flame spread and 50
smoke developed when tested in accordance with Underwriters
Laboratories 723 test method or ASTM E 84 test method.
Facing shall be composed of 38.1 micron white metallized
polypropylene film laminated to a fiberglass/polyester blend fabric with a fire resistant
adhesive. The resulting facing shall have a water vapor transmission rate of 1.15 ng/N·s
(ASTM E96, Procedure A), a beach puncture of 19.4 Joules and a mullen burst of 17.6
kg/cm². Tensile strength shall be 34.1 kn/m in the machine direction and 26.3 kn/m in the
cross-machine direction.
|
|