Architectural
Specifications - ARENASHIELD
|
ENGLISH |
|
Fiberglass shall be as outlined in the North American
Insulation Manufacturing Association (NAIMA 202-96) specification,
or equal, with an R-value of ______ when not compressed. The
fiberglass shall be faced with ______, as specified below, on one
side. The composite of fiberglass and facing shall have
surface burning characteristics not to exceed 25 flame spread and 50
smoke developed when tested in accordance with Underwriters
Laboratories 723 test method or ASTM E 84 test method.
Facing shall be composed of 0.0003" aluminum foil
laminated to a fiberglass/polyester blend fabric with a fire resistant adhesive. The
resulting facing shall have a water vapor transmission rate of 0.02 US perm (ASTM E96,
Procedure A), a beach puncture of 550 scale units and a mullen burst of 250 psi. Tensile
strength shall be 195# in the machine direction and 150# in the cross-machine direction. |
|
METRIC |
|
Fiberglass shall be as outlined in the North American
Insulation Manufacturing Association (formerly T.I.M.A )
specification, or P.E.B. 202 or equal, with an R-value of ______
when not compressed. The fiberglass shall be faced on one
side. The composite of fiberglass and facing shall have
surface burning characteristics not to exceed 25 flame spread and 50
smoke developed when tested in accordance with Underwriters
Laboratories 723 test method or ASTM E 84 test method.
Facing shall be composed of 7.6 micron aluminum foil
laminated to a fiberglass/polyester blend fabric with a fire resistant adhesive. The
resulting facing shall have a water vapor transmission rate of 1.15 ng/N·s
(ASTM E96, Procedure A), a beach puncture of 16.4 Joules and a mullen burst of 17.6
kg/cm². Tensile strength shall be 34.1 kn/m in the machine direction and 26.3 kn/m the
cross-machine direction.
|
|